Specifications for Single Phase UPS
Model |
ARS 110 |
Rating |
6KVA to 10KVA |
AC INPUT |
230V + 20% -15%, Single Phase Input |
Frequency |
50Hz ± 6% |
DC VOLTAGE: |
144/180/192V DC |
Charging Time |
12 Hours for 90% of full Capacity |
Charger Type |
CVCC (Constant Current Constant Voltage type) |
INVERTER: |
|
Technology |
DSP based, IGBT Switching |
Output Voltage |
230V AC single Phase |
Frequency |
50Hz ± 0.1Hz |
Waveform |
PWM Sine wave |
Harmonic Distortion |
Less than 3% on Linear Load |
Inverter Efficiency |
Upto 90% |
Power Factor |
0.8 |
Overload |
110 % for 5 min, 150% for 30 sec |
Crest Factor |
3 : 1 |
Audible Noise |
Less than 55 dB at 1 Meter |
DISPLAY : |
|
Digital LCD Display for |
Input and Output Voltages, Output currents & Frequency, DC Voltage , Battery and Load Percentage and All Faults |
GENERAL: |
|
Operating temperature |
0°C to 40°C |
Humidity |
Max 95%, Non-condensing |
PROTECTIONS : |
Output Overload & Short circuit, Output Under & Overvoltage, DC Under & Overvoltage, Mains Under & Overvoltage |
INDICATIONS & ALARMS: |
|
a) Mains on |
LED Indication |
b) Inverter |
LED Indication |
c) Batt Low |
LED Indication & Alarm |
d) Fault |
LED Indication & Alarm |
e) Overload |
LED Indication & Alarm |
BYPASS |
Manual Bypass provided, Static Bypass Optional |